๐Ÿ“‹ Standard Component Order

Components should follow the standard airflow path from intake to supply:

StepComponentFunction
1Fresh Air Damper / Mixing BoxAir intake control
2Pre-filter (G4)Coarse particle removal
3Main Filter (F7โ€“F9)Fine particle removal
4Heating CoilWinter air heating
5Cooling CoilSummer cooling & dehumidification
6HumidifierHumidity control (if needed)
7Fan SectionAir movement & pressure
8Sound AttenuatorNoise reduction
9HEPA FilterUltra-fine filtration (if needed)
10Inspection SectionMaintenance access

๐Ÿ—๏ธ Complete AHU Assembly

Complete AHU โ€” full workspace with all components configured
Complete AHU โ€” full workspace with all components configured
Complete AHU โ€” CAD schematic view
Complete AHU โ€” CAD schematic view

๐Ÿญ Manufacturing View

CTAPRO includes a manufacturing output module for production documentation.

Manufacturing โ€” configuration and BOM view
Manufacturing โ€” configuration and BOM view
Manufacturing โ€” production CAD drawing
Manufacturing โ€” production CAD drawing
Sizing Workflow โ€” from specification to production
Sizing Workflow โ€” from specification to production

โœ… Validation Checklist

Before generating an offer, verify all 8 points:

#CheckWhat to Verify
1โœ… All components placedComplete airflow path from intake to supply
2โœ… Psychrometry setSummer + winter conditions, correct altitude
3โœ… Face velocity OK2.5โ€“3.0 m/s โ€” green row in model table
4โœ… Filter ฮ”P acceptableCheck initial + final pressure drop
5โœ… Fan noise within limitsOffice โ‰ค70 dB(A), industrial โ‰ค85 dB(A)
6โœ… Attenuator addedIf fan noise exceeds target
7โœ… Construction specifiedMaterials, baseframe, drain pan, roof
8โœ… ZERO warningsWarnings panel must be completely clear
๐Ÿ’ก Tip Press F5 after every change. The #1 mistake is forgetting to recalculate before checking warnings.